?Q: What are the key acceptance criteria for JIAHUI fire doors during installation and final inspection???
?A:?? JIAHUI fire doors must comply with rigorous national and industry standards to ensure fire integrity, structural stability, and operational reliability. The acceptance process spans three phases: ?pre-installation checks, ?installation execution, and ?post-installation validation. Below are the critical criteria:
?1. Pre-Installation Preparation?
?Dimensional Compliance:
Wall opening dimensions must be verified before installation, with tolerances ??≤±5mm? in width/height. Deviations exceeding this require structural correction prior to door fitting.
?Embedded Components:
All pre-embedded steel plates (e.g., anchor points) must undergo ?full-penetration welding. Welded joints require complete anti-rust coating (e.g., epoxy primer) to prevent corrosion.
?2. Installation Execution?
?Alignment Precision:
Vertical deviation of the door frame: ??≤3mm per meter? (measured with a laser level).
Horizontal deviation: ??≤2mm per meter? (checked via precision level).
Frame misalignment compromises sealing and must be rectified immediately.
?Gap Management:
Clearance between door leaf and frame must be ??≤3mm? on all sides (hinge, lock, top). Gaps exceeding this require adjustment or reseating. All seams must be filled with ?intumescent fire sealant? (e.g., graphite-based strips) to block smoke/flame penetration.
?Closer Calibration:
After installation, door closers must enable automatic closure when the door is opened ?**≥90°. Closers failing to reset within ??≤60 seconds**? or exhibiting resistance >80N force are non-compliant.
?3. Final Inspection & Testing?
?Comprehensive Functional Checks:
?Seals: Fire-resistant seals (e.g., ceramic silicone strips) must adhere fully to the frame with ?zero gaps or peeling.
?Hardware: Hinges, locks, and closers must operate smoothly without jamming, deformation, or excessive force (>80Н). Внешний вид: Поверхности должны быть свободны от вмятин, ржавчины или дефектов покрытия (согласно Великобритания 12955-2008). Независимая проверка эксплуатационных характеристик: Двери, отобранные из партий (минимум 1 на 50 единиц), должны пройти независимые лабораторные испытания в соответствии с Великобритания/T 7633 или ISO 834, включая: Огнестойкость: Сохранение структурной целостности и теплоизоляции в течение расчетного времени (например, 90 мин для класса А). Утечка дыма: Утечка воздуха ≤1,5 ??м3/(м·ч) при перепаде давления 50 Па. Отчеты об испытаниях должны быть представлены до утверждения проекта. Документация и соответствие требованиям. Обязательные документы: заводские сертификаты (сертификаты ISO/ФМ), протоколы испытаний продукции и журналы монтажа. Сертификаты сторонней инспекции на огнестойкость и герметичность. Обработка несоответствий: двери, не прошедшие какой-либо контрольный пункт, требуют устранения дефектов (например, повторной герметизации, замены фурнитуры) и повторной проверки. Повторные нарушения приводят к отбраковке партии.